Honeywell Ha40py | 4-channel | Multi-point Controllers | Gasdetectorsusa
Gas Leak and Flame Detectors, Analyzers, Alarm Devices and Calibration Gas

HONEYWELL   HA40PY

HONEYWELL HA40PY
  • DESCRIPTION
  • FEATURES
  • SPECIFICATIONS
  • LITERATURE
Honeywell HA40 Digital Gas Detection ALARM CONTROLLER, with 4 channels and LCD display of 128x64 pixels. Has configurable control, flexible application and an user-friendly operation. UL/CSA approved, Class I, Division 2 - NEMA 4X, painted steel or stainless steel enclosure with magnetic input for nonintrusive control. Includes 2 (5 Amp) Common Relays, Part No. 10-0222 6 discrete relays, Part No. 10-0315 Internal 50W Power Supply and Part No. 10-0221-4 4-Channel 4-20 mA Input (bridge option). *** Phased Out Replaced by TouchPoint Plus***

Inquiry

FEATURES

Enhanced Technology
  • Accepts inputs from up to four 4-20mA sensors transmitters. Generates 24 VDC @ 8 watts external device power
Fit for Purpose
  • CSA certified to C22.2 NO. 152 for combustible detection and Class I, Div. 2, Groups A,B,C,D CE
  • Touch & magnetic keypad for nonintrusive operation in potentially hazardous locations
  • NEMA 4X (Div. 2 certified) and Explosion-Proof wall mount packaging options available
  • Three standard SPDT common alarm relays for HORN, HIGH, WARN or FAULT
Advanced Communications
  • 3 independent alarm levels per channel. Relay Acknowledge feature allows silencing of external audible devices during existing alarm conditions
  • Graphic LCD readout displays monitored data as bar graphs, trends and engineering units. Alarm LED's flash when new and become steady after acknowledged
  • Cal Mode offers pushbutton zero / span calibration for direct sensor interface applications. Authorization Mode allows locking of critical configuration variables

The HA40 digital gas controller provides simultaneous display and alarm functions for four sensor transmitters, along with user-friendly operation and configuration flexibility.

The HA40 accepts sensor inputs for gas concentration and other atmospheric data. It can function as a standalone device or can be integrated into a fire and gas system. The controller features NEMA4X enclosures and meets Class I, Div. 2, Groups A,B,C,D requirements. Explosion-proof wall mount packaging options are also available.

The controller features a large, graphic LCD readout that displays monitored data as bar graphs, trends and engineering units. A touch-and-magnetic keypad allows for non-intrusive operation in potentially hazardous locations. Cal Mode offers pushbutton zero/span calibration for direct sensor interface applications. Authorization Mode allows locking of critical configuration variables.

Other standard features include Modbus TCP/IP communications, three independent alarm levels per channel, alarm relays, flexible mounting options and 4-20m inputs. The 4-20mA inputs are ideal for interfacing to sensor transmitters that may be long distances from the controller. 24 VDC @ 8 watts provides external device power. The controllers accept inputs from two local or remote mounted sensors or transmitters.

Enclosures

H20 Enclosures

General Specifications
Use Wall or rack/panel mountable digital gas controller for industrial or commercial use
Display 128 x 64 pixel graphic LCD with backlight displays, bar graphs, trends and engineering units
Common Alarm Relays (standard) Two, 5 amp 30VDC or 250VAC resistive Form C
Discrete Alarm Relays Six 5 amp 30VDC or 250VAC resistive Form C
Analog Output (Optional) 10 bit 4-20mA output. Max load 800 ohms with nominal 24VDC power supply.
Serial Port (Optional) Slave RS-485 port equipped with Tx / Rx LED's
Protocol = Modbus RTU
Power Requirement 100-240 VAC / 24 VDC are standard primary power supplies
Operating Temperature Range (-25 °C to +50 °C)
Housing Options NEMA 4X / IP66 wall mount approved for Div 2
NEMA 7 explosion-proof wall mount Div 1 & 2
NEMA 4X SS Enclosure wallmount approved for Div 2
Weight NEMA 4 = 5 pounds, NEMA 7 = 40 pounds
Warranty 2 Years Limited
Wireless Options An optional HA40 900MHz wireless interface (10-2454) can be used to communicate with an HA71 master Modbus controller.
An additional 900MHz wireless adapter is also required for the HA71 (10-0288).
Certified to CSA C22.2 No. 1010.1 & ISA S82.02; UL 1604 / C22.2 No 213 (NEMA 4X = Div 2 Groups A, B, C, D, NEMA 7 = Groups B, C, D); EN55011 & EN61000.
Export Info
Harmonized Tariff Code (HTC)8531100045
> 4-CHANNEL :    3 Items found.
S-DP4
(6764)

PROSENSE  S-DP4

Prosense S-DP4 Gas Detector Controller, Alarm Panel for Up to 4 Analog 4-20 mA gas detectors. Monitors explosive (LEL) and toxic(ppm, %VOL), Alarm and Fault LED indicators for each detector and buzzer. Fault, Alarm1, Alarm2 and AUX Relays. Optional Modbus RS485 output and Alarm/Fault Relays for each channel. Polycarbonate Housing, IP66

Configure

$772.20 
S-DPX004
(7030)

PROSENSE  S-DPX004

Prosense S-DPX004 Gas Detector Controller, Alarm Panel for 4 x 4-20mA Channels, OLED Display, Alarm and Fault LED indicators for each detector and buzzer. Includes Modbus RTU RS485 output, 5 common alarm relays: Fault, Alarm-1, Alarm-2, Alarm-3 and overrange. Polycarbonate Housing, IP66.

Configure

$900.90 
90-50
(1642)

RC SYSTEMS  90-50

RC Systems ViewSmart 400 4-Channel Gas Detector Integral Alarm Controller with standard 2x 5A SPDT relays, with 6 x optional alarm relays, in standard CSA approved, Class I, Division 2 - NEMA 4X non-metallic enclosure. 120VAC or 24VDC power supply. Modbus interface. Optional 4 x 3-wire bridge or 4 x 4-20mA input channels board.

Configure

$3,525.97 
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.