Gds C2/tx/1-1/0-0/1-1-0900 | 32-channel Wireless | Multi-point Controllers | Gasdetectorsusa
Gas Leak and Flame Detectors, Analyzers, Alarm Devices and Calibration Gas

GDS   C2/TX/1-1/0-0/1-1-0900

GDS C2/TX/1-1/0-0/1-1-0900
  • DESCRIPTION
  • FEATURES
  • SPECIFICATIONS
  • LITERATURE
GDS C2/TX Multi-Channel Wireless Display & Alarm Controller for Critical Gas Monitoring Applications. Monitors up to 32 GASMAX TX detectors. Large LCD Display. 900 MHz or 2.4 GHz FHSS radios. 8 Standard programmable relays. 24VDC or 117/240VAC. Optional MODBUS slave port. Class I Div 2 NEMA 4X or NEMA 7 enclosure.

Inquiry

Features

  • Monitor up to 32 GASMAX TX toxic or combustible gas detectors
  • Large LCD display shows values, alarm status and setup information
  • 900 MHz or 2.4 GHz FHSS radios for long distance communications
  • Channel info uploaded from GASMAX TX simplifies setup
  • Eight standard programmable relays for alarm, fault, low batt
  • Operates on either +24VDC or 117/240VAC 50/60Hz
  • Optional RS-232 or RS-485 serial MODBUS ® slave port
  • Optional data logging with USB interface for easy data transfer
  • Optional 802.11b/g WiFi web server for smartphone access
  • Optional satellite / cellular remote access modem with antenna
  • Non-metallic, painted steel and stainless steel enclosures
  • Alarm Ack button doubles as “Push to Test” for relays
  • Touch and magnetic keys for non- intrusive operation in XP areas
  • 900 MHz transmitter power adjustable from 10mW to 1 watt
  • MODBUS port for easy interface from DCS or MODBUS master
  • Manufactured in USA

The new C2/TX Wireless Site Manager is the heart of third-generation wireless systems from GDS Corp. Designed to monitor from 1 to 32 wireless GASMAX TX gas detectors, the C2/TX incorporates the latest features while retaining the reliability and cost effectiveness of previous generation products.

The C2/TX WSM and GASMAX TX gas monitor have been designed from the ground up to deliver the best wireless solution for toxic and combustible gas detection available. Designed specifically for use with the new GASMAX TX gas monitor, the C2/TX controller features a high resolution LCD display and eight relays that can be programmed to signal multiple alarm levels, sensor fault, communications fault or low battery.

Digitally Connected, Wireless Enabled

Unlike mesh networks and other systems designed for short range applications, the C2/TX utilizes Frequency-Hopping Spread Spectrum (FHSS) modems that offer higher power, longer range and lower susceptibility to interference. An optional multi-interface board supports an RS-232 or RS-485 wired serial port for remote MODBUS access, a solid-state data logger with USB interface, a second 900 MHz or 2.4 GHz radio for dedicated wireless remote access as well as an 802.11 WiFi interface for access via smartphones or tablets. WiFi-enabled C2/ TX controllers also feature an integrated web server that allows users to remotely view real-time data, historical information and current configuration. With the correct password, remote users can change system setup variables. Finally, an optional satellite / cellular modem enables remote access from anywhere in North America.

Simplified Setup

Unlike previous generation products that required both the controller and gas detector be individually configured for gas type, engineering units, range and other parameters, the C2/TX automatically uploads the setup information from each GASMAX TX gas monitor. This reduces the possibility of errors and simplifies initial setup.

Reliability

The C2/TX controller is designed for use in Class I Division 2 hazardous areas. An optional NEMA 7 enclosure allows use in Class I Div 1 areas. Up to 12 watts of 24 VDC power is available for auxiliary devices or transmitters. In addition, an auxiliary 50 watt DC supply is available.

Power Input 24VDC (12 Watt MAX) 85-240 VAC power supply in- cluded; up to 12W available for powering remote or local sensors
Optional 50W supply available for local lights, horns or other anciliary devices
DisplayBacklit 128x64 pixel LCD display
InputWireless 900 MHz or 2.4 GHz transmissions from up to 32 single channel GASMAX TX monitors or 16 dual channel GASMAX TX gas monitors
Relay OutputEight programmable output relays (SPDT 5A @ 30VDC / 240VAC resistive load)
Digital OutputOptional RS-232 or RS-485 wired MODBUS port
Optional WiFi 802.11 b/g wireless interface with built-in web server
Optional second 900 MHz or 2.4 GHz wireless modem for dedicated remote communciations
Optional data logging with USB interface
Audible OutputOptional local piezo / horn (see option “C”)
Visual OutputOptional local strobe (see option “D”)
Temp-25°C to +50°C operating
HousingAvailable in non-metallic, painted steel and stainless steel enclosure; also available in NEMA 7 explosion proof enclosure. Sunshade recommended if unit is to be installed in direct sunlight or areas where temperature extremes may be expected.
DimensionsNEMA 4X Non-metallic: 11.25” x 13.31” x 7.25”
NEMA 4X – Painted or stainless: 9.84” x 13.65” x 6.2”
NEMA 7: Width 13” x 14.25” x 6.25”
ApprovalsApprovals pending
Export Info
Harmonized Tariff Code (HTC)8531100045
Cookie Notice

This online store uses cookies to remember users, enable checkout and to collect aggregate information that allows us to analyze traffic patterns on our site (no personal information is stored). For more information you can read our Privacy Policy.