The Cooper MEDC-Hawco heat detector has been designed for use in
hazardous environments. These units are suitable for fire alarm and/or
suppression systems in offshore and onshore applications including paint
spray booths, flammable material stores, turbine rooms, extract ductwork
and other hazardous areas throughout the oil & gas, petrochemical and
process industries.
Comprising a Fenwal rate-compensated detector with all-stainless steel
external construction, mounted to either a type SM87 marine grade alloy
enclosure (Exd version) or JB10 corrosion-free GRP enclosure (Exia,
Exem/UL versions). The contact in the detector CLOSES at alarm
temperature.
To select appropriate temperature setting see specification on reverse.
FEATURES
- Zone 0, Zone 1 and Zone 2 use.
- ATEX Approved
- EExd IIB T3/T6
- Exd IIC
- EExem II T4/T6
- EExia IIC T4/T6
- UL listed for USA and Canada
- Class I, Div 2, Groups A-D.
- GOST ‘R’ & ‘K’ certified.
- Chinese (CQST) certified.
- Brazilian (Inmetro) certified.
- IP66 & IP67.
- Certified temperature:
- –20°C to +125°C (Exd)*.
- –20°C to +55°C (Exem/UL).
- –55°C to +55°C (Exia).
- Stainless steel probe.
- Detector temperature settings: 60°C to 385°C,
(140°F to 725°F).
- Marine grade alloy or GRP enclosure.
- Optional guard.