GENERAL SPECIFICATIONS |
Spectral Response | Three IR Bands
|
Detection Range (at highest Sensitivity Setting for 1ft2 (0.1m2) pan fire) |
Fuel |
ft / m |
n-Heptane |
215 / 65 |
Gasoline |
215 / 65 |
Diesel Fuel |
150 / 45 |
JP5 |
150 / 45 |
Kerosene |
150 / 45 |
Ethanol 95% |
135 / 40 |
Methanol |
115 / 35 |
IPA (Isopropyl Alcohol |
135 / 40 |
Methane* |
100 / 30 |
LPG (Liquid Propane Gas)* |
100 / 30 |
Polypropylene Pellets |
16 / 5 |
Office Paper |
33/ 10 |
* 20" (0.5m) high, 8" (0.2m) width plume fire |
|
Response Time | Typically 5 seconds
|
Adjustable Time Delay | Up to 30 seconds
|
Sensitivity Ranges | 4 Sensitive ranges for 1 ft 2 (0.1m2) n-heptane pan fire from 50 ft (15m) to 215 ft (65m)
|
Field of View | Horizontal 100º; Vertical 95º
|
Built-in-Test (BIT) | Automatic (and Manual)
|
Temperature Range | Operating: -67ºF to +167ºF (-55ºC to +75ºC) Option: -67ºF to +185ºF (-55ºC to +85ºC) Storage: -67ºF to +185ºF (-55ºC to +85ºC)
|
Humidity | Up to 95% non-condensing (withstands up to 100% RH for short periods)
|
Heated Optics | To eliminate condensation and icing on the window
|
ELECTRICAL SPECIFICATIONS |
Operating Voltage | 24 VDC nominal (18-32 VDC)
|
Power Consumption | Standby: Max. 100mA (150mA with heated window) Alarm: Max. 150mA (200mA with heated window)
|
Cable Entries | 2 x 3/4" - 14NPT conduits or 2 x M25 x 1.5 mm ISO
|
Wiring | 12 - 22AWG (2.5mm 2 - 0.3mm 2)
|
Electrical Input Protection | According to MIL-STD-1275B
|
Electromagnetic Compatibility | EMI/RFI protected to EN50130-4
|
Electrical Interface | The detector includes twelve (12) terminals with five (5) wiring options (factory set)
|
OUTPUTS |
Relays | Alarm, Fault and Auxiliary SPST volt-free contacts rated 5A at 30 VDC or 250 VAC.
|
0-20mA (stepped) | Sink (source option) configuration
Fault: 0 +1mA
BIT Fault: 2mA ± 10%
Normal: 5mA ± 10%
Warning: 10mA ± 5%
Alarm: 15mA ± 5%
Resistance Loop: 100-600 Ω |
HART Protocol |
HART communication on the 0-20mA analog current (FSK) - used for maintenance, configuration changes and asset management
|
RS-485 | RS-485 Modbus compatible communication link that can be used in computer controlled installations
|
MECHANICAL SPECIFICATIONS |
Materials Enclosure options | - Stainless Steel 316L with electro polish finish - Heavy duty copper free aluminum (less than 1%), red epoxy enamel finish |
Mounting | Stainless Steel 316L with electro polish finish
|
Dimensions | Detector 3.5" x 4.5" x 6.1" (90 x 114 x 156 mm)
|
Weight | Detector (St.St.) 5.5 lb (2.5 kg) Detector, aluminum 2.5 lb (1.2 kg) Tilt mount 2.2 lb (1.0 kg)
|
Environmental Standards | Meets MIL-STD-810C for Humidity, Salt & Fog, Vibration, Mechanical Shock, High Temp, Low Temp
|
Water and Dust | IP66 and IP67 per EN60529, NEMA 250 6P
|
APPROVALS |
Hazardous Area |
ATEX and IECEx |
Ex II 2 GD, |
|
|
Ex de IIB+H2 T5 o (-5+55 ºCºC 7 |
x de IIB+H2 T4 (-55ºC to + 85ºC) |
|
Ex tD A21 IP66/X7 T 95ºC |
Ex tD A21 IP66/X7 T 105ºC |
FM / CSA |
Class I Div. 1, Groups B, C & D |
|
|
Class II/III Div. 1, Groups E, F & G |
|
|
Performance | EN54-10 (LPCB) FM-3260 (FM) DNV Marine Approval
|
Reliability | IEC61508 - SIL2 (TUV)
|
ACCESSORIES |
Fire Simulator | 20/20-310
|
Weather Protector | 777163 |
Laser Pointer (Detector area coverage) | 777166 |
Tilt Mount | 40/40-003 |
Air Shield | 777161 |